- AC power
- 77 kW
- Efficiency
- 98.7 %
- Enclosure rating
- IP65
- Weight
- 60 kg
SUN-70K-G: inverter by Deye, part of the series SUN-60-80K-G.
Key specifications: AC power: 77 kW; Efficiency: 98.7 %; enclosure rating: IP65; weight: 60 kg.
A WINDER engineer will confirm availability, delivery time and price on request.
Technical specifications SUN-70K-G
- Operating Temperature
- -25 ~ +65 ℃
- Transformer
- Transformerless
- Protection Class
- IP65
- Humidity
- 0-100 %
- Cooling
- Fan
- Max. Altitude
- 2000 m
- Interface
- RS 232, RS 485, WLAN
- Display
- LCD
- Protection Features
- Anti Island Protection(ENS), Short Circuit Protection, Overvoltage Protection, Overcurrent Protection, Overtemperature Protection, Reverse Polarity Protection, Surge Protection, Ground Fault Monitoring, Isolation Monitoring
- Max. DC Power
- 91 kW
- Max. DC Voltage
- 1000 V
- Min. DC Voltage to Start Feed In
- 250 V
- Max. DC Current
- 160 A
- MPP(T) Voltage Range
- 200~850 V
- No of MPP Trackers
- 4
- DC Inputs
- 16
- Connectors
- MC4
- Max. AC Power
- 77 kW
- Output AC Voltage Range
- 277~460 V
- Nominal AC Voltage
- 400 V
- Frequency Range
- 47-62 Hz
- Frequency
- 50, 60 Hz
- Power Factor (cosθ)
- 1
- Distortion (THD)
- < 3 %
- No of feed-in phases
- 3
- Max. Efficiency
- 98.7 %
- Euro Efficiency
- 98.3 %
- Dimensions (H/W/D)
- 575x700x297 mm
- Weight
- 60 kg
- Power Consumption at Night
- < 1 W
- Noise Level
- < 55 dB(A)
Models in the series SUN-60-80K-G
| Model | AC power | Phases | Efficiency |
|---|---|---|---|
| SUN-60K-G | 66 kW | 3 | 98.7 % |
| SUN-70K-G | 77 kW | 3 | 98.7 % |
| SUN-75K-G | 82.5 kW | 3 | 98.7 % |
| SUN-80K-G | 88 kW | 3 | 98.7 % |
Data is taken from the manufacturer’s datasheet (Deye) and may change without notice. Before you order, a WINDER engineer will check the specifications against the current document.
Similar specificationsInverters 50–100 kW · 385
- 36–66 kW398.5 %Request a quote
- 50–60 kW3up to 98.7 %Request a quote
- 29.9–50 kW397.8 %Request a quote
Find a solar power system for your site
We will estimate generation, select compatible panels, an inverter and batteries, then design and install your turnkey system.